Model Name |
APC Smart-UPS Modular Ultra 15kW Scalable to 15kWN+1 Redundant, Tower, 120+208/240V, 24U Rack |
Other Model Details |
APC Smart-UPS Modular Ultra 15kW Scalable to 15kW N+1 Redundant, Tower, 120+208/240V, 24U Rack Factory Serviced,SRYL15K15XLT24W,; Std Exch APC Smart-UPS Modular Ultra 15kW Scalable to 15kW N+1 Redundant, Tower, 120+208/240V, 24U Rack,SRYL15K15XLT24Q, |
Updated On |
2023-10-22 |
Last Update |
2023-10-23 |
UPC |
731304420132 |
Power Conversion Mechanism |
Static |
Minimum Configuration Tested Model Number |
SRYL5K15RMXLT |
Active Output Power Rating Minimum Configuration (W) |
5000 |
Apparent Output Power Rating Minimum Configuration (VA) |
5000 |
Maximum Configuration Tested Model Number |
SRYL15K15RMXLT |
Active Output Power Rating Maximum Configuration (W) |
15000 |
Topology (ac) |
Multi-Mode Double Conversion |
Topology and Product Type Combined |
ac – Other |
Application |
Commercial |
Rated Input Voltage (V rms) |
208-240 |
Rated Input Frequency (Hz) |
50-60 |
Rated Output Voltage (V) |
208-240 |
Rated Output Frequency (Hz) |
50-60 |
Rack Mountable |
No |
Rack Mount Height (U) |
24 |
Height (mm) |
1199 |
Width (mm) |
600 |
Depth (mm) |
900 |
Normal Mode(s) Input Dependency Characteristic (ac) |
Voltage and Frequency Independent, Voltage and Frequency Dependent |
Modular UPS |
Yes |
Number of Normal Modes |
Multiple-normal-mode |
Default Normal Mode (ac) |
Voltage and Frequency Independent |
Test Input Voltage (V rms) |
240 |
Test Input Frequency (Hz) |
60 |
Test Output Voltage (V) |
240 |
Test Output Frequency (Hz) |
60 |
Total Input Power in W at 0% Load Min Config Lowest Dependency (ac) |
72.4 |
Total Input Power in W at 0% Load Min Config Highest Dependency (ac) |
75.2 |
Efficiency at 25% Load Min Config Lowest Dependency (ac) |
92.8 |
Efficiency at 25% Load Min Config Highest Dependency (ac) |
93.7 |
Efficiency at 50% Load Min Config Lowest Dependency (ac) |
94.9 |
Efficiency at 50% Load Min Config Highest Dependency (ac) |
96.4 |
Efficiency at 75% Load Min Config Lowest Dependency (ac) |
95.1 |
Efficiency at 75% Load Min Config Highest Dependency (ac) |
97.4 |
Efficiency at 100% Load Min Config Lowest Dependency (ac) |
94.7 |
Efficiency at 100% Load Min Config Highest Dependency (ac) |
97.8 |
Weighted Efficiency Calc Min Config Lowest Dependency |
94.9 |
Weighted Efficiency Calc Min Config Highest Dependency |
97.2 |
Minimum Configuration Input Power Factor Lowest-Input Dependency |
1 |
Minimum Configuration Input Power Factor Highest-Input Dependency |
1 |
Total Input Power in W at 0% Load Max Config Lowest Dependency (ac) |
153.2 |
Total Input Power in W at 0% Load Max Config Highest Dependency (ac) |
164.4 |
Efficiency at 25% Load Max Config Lowest Dependency (ac) |
94.2 |
Efficiency at 25% Load Max Config Highest Dependency (ac) |
95.1 |
Efficiency at 50% Load Max Config Lowest Dependency (ac) |
95.5 |
Efficiency at 50% Load Max Config Highest Dependency (ac) |
97.1 |
Efficiency at 75% Load Max Config Lowest Dependency (ac) |
95.4 |
Efficiency at 75% Load Max Config Highest Dependency (ac) |
97.8 |
Efficiency at 100% Load Max Config Lowest Dependency (ac) |
94.9 |
Efficiency at 100% Load Max Config Highest Dependency (ac) |
98.1 |
Weighted Efficiency Calc Max Config Lowest Dependency |
95.1 |
Weighted Efficiency Calc Max Config Highest Dependency |
96.8 |
Maximum Configuration Input Power Factor Lowest-Input Dependency |
1 |
Maximum Configuration Input Power Factor Highest-Input Dependency |
1 |
Efficiency (%) |
94.9 |
Modular UPS Module Tested Model Number |
SRYL5KPMT |
Energy Storage Mechanism |
Battery |
Energy Storage System Technology |
Lithium-ion Battery |
Energy Storage System Configuration |
Integral |
Energy Storage System Removable to Another Room |
No |
Energy Storage System Runtime at 100% Load (min.) |
5 |
Energy Storage System Runtime at 50% Load (min.) |
12 |
Energy Storage System Warranty (yrs) |
5 |
Reviews